![]() ![]() ![]() The choices are MOD/ACS, ON/OFF LINE, and MODULATION ONLY. If the lead/lag set point is set to lag (see 3.5.1), the value of the lag offset will be subtracted from the online and offline setpoints.ģ.5.5 Mode of Operation- This setpoint is used to select the operating mode of the compressor. If set to lag, the controller will subtract the lag offset (see 3.5.4) from the online and offline set points and operate the compressor at the lower pressure range.ģ.5.2 Offline Pressure- This setpoint is the pressure the compressor will unload at if it is operating in on/off line mode.ģ.5.3 Online Pressure- This setpoint is the pressure the compressor will load at.ģ.5.4 Lag Offset- This setpoint is used with the lead/lag operation. If set to lead, the controller will load and unload the compressor by the online and offline setpoints. 3.5.1 Lead/Lag- This setpoint is used for setting lead or lag operation. ![]()